DYNAMIC RG20PS

Add item to your basket

Overall Performance
PRP Continuous Power kVA16
PRP Continuous Power kW16
LTP Stand-by Power kVA18
LTP Stand-by Power kW18
Power factor cos 1.9
Voltage VAC230
Frequency Hz50
Ampere PRP/LTP70/77
Speed RPM 1500
  Dimensions and noise level
Length mm 1930
Width mm800
Height mm 1230
Weight kg650
Gross Weight kg -
Sound pressure at 7 mt dBA-
 
Engine General Data
Engine Brand Perkins
Model 404A-22G1
PRP Power at the flywheel kW18.40
LTP Power at the flywheel Kw20.30
Fuel Diesel oil
Nr. Cylinders 4
Air intake Aspirated
Cooling Water
Cubic Capacity l. 2.22
Speed regulationMechanical
Regulator precision +/- %0.75
Voltage VDC12
Loud Step G1 – KWe-           
Loud Step G2 – KWe-           
Loud Step G3 – KWe-           
Emissions  -
  Alternator General Data
Alternator brand Mecc-Alte
Model ECP26-2L/4A
Type of excitation Self-excited
Type of regulation AVR
Regulator precision +/- %1.00
Structure Data
Type of structure DYNAMIC
Tank Capacity L70
Retention Basin Yes
Exhaust diameter mm50
  Fuel Consumption
Consumption 25% l/h0.00
Consumption 50% l/h 2.90
Consumption 75% l/h 4.00
Consumption 100% l/h 5.30
Autonomy at 75% of load h. = 18 h
  Engine liquids and equipment
Type of lubricant Oil SAE 15W40
Lubricant capacity l.*10.60
Type of coolant Antifreeze liquid
Coolant capacity l.*7.00
Ait intake filter Paper cartridge
Battery capacity Ah45
Number of batteries*1
  Fuel System and Energy Balance
AC pump suction head kPa1
Combustion air flow volume LTP m3/min1.45
Cooling air capacity LTP m3/min40.20
Exhaust gas flow-density LTP m3/min3.94
Exhaust gas temperature LTP *C505.00
Brake mean effective pressure kPa10.20
Energy to exhaust LTP kWt16.60
Energy to coolant LTP kWt 19.60
Energy to radiation LTP kWt 4.40
Alternator General Data
Alternator brand Mecc-Alte
Model ECP26-2L/4A
Type of excitation Self-excited
Type of regulation AVR
Regulator precision +/- %1.00
 
Control Panel Features QFIA-4520 Protection Cover Circuit breaker AMF Controller DSE4520
  • Voltmeter, Frequencymeter, Ammeter
  • Generator power (kW, kV Ar, kV A & pf) monitoring
  • Hour meter
  • Fuel level meter
  • Overload (kW & kV Ar) protection
  • Low oil pressure protection
  • High coolant temperature protection
  • Low fuel level protection
  • Battery charger alternator fault
  • Rpm protection
Emergency stop button Terminal board for ATS connection Battery charger On/off switch
Heavy duty rubber anti-vibration mountings
Fuel tank with drain plug and retention basin
Canopy: Sandblasting and cataphoresis treatment of intake / exhaust grids
Canopy: Central lifting hook
Muffler: Super silent, Residential type, integrated in the canopy - With aluminium coating
Control Panel: - Metal Control panel with protective back cover - Dedicated area to make easier the electrical connection to the load
PRP Continuous power kVA16
PRP Continuous power kW16
LTP Stand-by power kVA18
LTP stand-by power kW18
Power factor cos fiφ1.0
Voltage VAC230
Frequency (Hz)50
Ampere PRP/LTP70 / 77
Speed RPM1500

Have you a Question?

Call us on: (0504) 44437
email info@egps.ie
or simply fill out the form below